DC400 Dispensing Cutoff System404-4 Controller Installation InstructionsFranklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608 8
10Page intentionally blank
11Page intentionally blank
©2011 000-0316 Rev A
2Important Safety MessagesFranklin Fueling Systems (FFS) equipment is designed to be installed in association with volatile hydrocarbon liquids such a
3Product DescriptionThe DC400 system uses a sump sensor to detect the presence of liquid in the STP (Submersible Turbine Pump) or dispenser sump. If l
4Installation for Submersible Pump CutoffNotice! Only qualied service technicians experienced with petroleum dispensing and pumping systems should in
53. Remove the STP junction box cover / plug. Make sure the STP junction box has enough room to accommodate the additional 404-4 controller wires (se
6Installation for Alarm WiringImportant! For all applications, do not exceed the relay contact rating of 250VAC, 12A. The relay contacts (Orange / Bl
7Dispenser-Specic WiringDispenserBreakerORG/BLKORGBLKWHTSensor404-4 Controller12A, 240VACHNGGGRN/YELGRN120-240VAC123456789101112Main Junction BoxW-VF
8Figure 10: 404-4 Wired to a Gilbarco Encore 300 or 500 DispenserFigure 9: 404-4 Wired to a Gilbarco Eclipse DispenserORG/BLKORGBLKWHTSensor404-4 Cont
9Figure 11: 404-4 Wired to a Tokheim 262 or 262A DispenserDispenserBreakerORG/BLKORGBLKWHTSensor404-4 Controller12A, 240VACGGGRN/YELGRN120-240VACMain