ColibriAutomatic Tank GaugeCL6 SeriesInstallation Guide Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608 838 8786 • 800 2
7Communication PortsThe Colibri console has several communication ports that can be used to communicate with devices. The communication ports can be u
Control Drawing
©2009 FFS 000-2153 Rev. B
Copyright ©2009 by Franklin Fueling Systems (FFS). No part of this publication may be reproduced in any form without the prior written consent of FFS.
ContentsImportant Safety Messages ...1Introduction
1Important Safety MessagesFFS equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fuel.
2IntroductionThis manual contains installation and site preparation instructions for FFS’s Colibri console. Safety issues, troubleshooting information
3Console DimensionsFigure 2: Console Dimensions(235 mm)9.25"1.00"(25.4 mm)2X 0.21"(5.33 mm)Ground studSee note 2.2Intrinsically safe wi
44Standard Installation MaterialsCircuit Breaker20 Amp — providing power only for the consoleWeatherproof Junction BoxesMinimum 16 cubic inch (406.4 c
5Wiring the Console Intrinsically Safe WiringNon-intrinsically safe wiring cannot be run in the same conduit as intrinsically safe wiring. Probe Wirin
6Line Power WiringNon-Intrinsically Safe WiringAlways lock out and tag electrical circuit breakers while installing or servicing this equipment and an