TS-550 evo®Fuel Management SystemInstallation Guide Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608 838 8786 • 800 225 9
10Wiring the Console & ModulesConduit must only enter the console enclosure through the designated knockouts as shown below in Figure 4. COMM 2BUS
11Controller Module (CM)The Controller Module (CM) is a non-intrinsically safe module that acts like the brain of your console. The CM handles all of
12110 / 240 VAC Line Power Wire Connection ListElectrical Panel No. Conductors, Color (Gauge)Circuit20 Amp Circuit Breaker1 Black wire, 14 AWG (1.6 mm
13Relay Output Wiring (optional)As illustrated in the diagram below, the Power Supply Module’s two relay outputs can be used to activate an external a
14Non-Standard Power RequirementsThe console’s power must be maintained on a power transfer supply for emergency backup generator applications. In add
15Relay Module (RLY)The RLY is a non-intrinsically safe module that has 8 identical Form C output channels. Each channel has a fuse and three terminal
16AC Input Module (ACI)The ACI is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can be used for disp
17Input/Output Module (IO)The Low Voltage Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage input
1810 Amp Relay Module (10ARLY)The 10 Amp Relay Module is a non-intrinsically safe module that has 6 identical Form C output channels. Each channel has
19Intrinsically Safe Module WiringAlways lock out and tag electrical circuit breakers while installing or servicing this equipment and any related equ
2Important Safety MessagesFranklin Fueling Systems equipment is designed to be installed in association with volatile hydrocarbon liquids such as gaso
20Probe Module (PRB)The Probe Module (PRB) gathers data from probes and presents that information to the Controller Module (CM) for use in inventory r
212-Wire Sensor Module (2WSNS)The 2-Wire Sensor Module (2WSNS) is designed to accept 12 sensor inputs per module, and the system as a whole can accept
223-Wire Sensor Module (3WSNS)The 3-Wire Sensor Module (3WSNS) is designed to accept 8 sensor inputs per module, and the system as a whole can accept
234-20mA Analog Input Module (420IB)The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. The TS-550
24Control Drawing
26WarrantyFor information concerning Franklin Fueling Systems’s warranties, please refer to the Franklin Fueling Systems Fuel Management Systems Warra
27SpecicationsThe TS-550 evo console must be mounted in a location where explosive or ammable vapors are not present, otherwise an explosion hazard
©2011 FFS 000-2170 Rev. A
3Copyright ©2011 by Franklin Fueling Systems (FFS). No part of this publication may be reproduced in any form without the prior written consent of FFS
4ContentsImportant Safety Messages ...2Notice ...
5IntroductionThis manual contains installation and site preparation instructions for Franklin Fueling Systems’s TS-550evo console. Overall safety issu
6Standard Installation MaterialsRecommended standard materials should be selected and installed per all applicable local, state and federal codes gove
7Probe Installation Kit(s)See the TSP-LL2’s installation instructions that came with the probe for the items included with the TSP-K4A standard probe
8TS-550 evo Dimensions and Operating ParametersThe TS-550 evo has conduit knockouts and communication ports located on the bottom of the unit. Use the
9Communication PortsThe TS-550 evo console has several communication ports that can be used to communicate with various devices. The communication por