Page 1 - TS-550 evo

TS-550 evo®Fuel Management SystemInstallation Guide Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel:  +1 608 838 8786 • 800 225 9

Page 2 - Important Safety Messages

10Wiring the Console & ModulesConduit must only enter the console enclosure through the designated knockouts as shown below in Figure 4. COMM 2BUS

Page 3 - Inspection of Materials

11Controller Module (CM)The Controller Module (CM) is a non-intrinsically safe module that acts like the brain of your console. The CM handles all of 

Page 4 - Contents

12110 / 240 VAC Line Power Wire Connection ListElectrical Panel No. Conductors, Color (Gauge)Circuit20 Amp Circuit Breaker1 Black wire, 14 AWG (1.6 mm

Page 5 - Product Description

13Relay Output Wiring (optional)As illustrated in the diagram below, the Power Supply Module’s two relay outputs can be used to activate an external a

Page 6

14Non-Standard Power RequirementsThe console’s power must be maintained on a power transfer supply for emergency backup generator applications. In add

Page 7 - Console Installation

15Relay Module (RLY)The RLY is a non-intrinsically safe module that has 8 identical Form C output channels. Each channel has a fuse and three terminal

Page 8 - Console Operating Parameters

16AC Input Module (ACI)The ACI is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can be used for disp

Page 9 - Communication Ports

17Input/Output Module (IO)The Low Voltage Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage input

Page 10 - Safe Knockouts

1810 Amp Relay Module (10ARLY)The 10 Amp Relay Module is a non-intrinsically safe module that has 6 identical Form C output channels. Each channel has

Page 11 - Power Supply Module (PS)

19Intrinsically Safe Module WiringAlways lock out and tag electrical circuit breakers while installing or servicing this equipment and any related equ

Page 12 - Stud: #8 threaded post

2Important Safety MessagesFranklin Fueling Systems equipment is designed to be installed in association with volatile hydrocarbon liquids such as gaso

Page 13 - RELAY OUTPUTS

20Probe Module (PRB)The Probe Module (PRB) gathers data from probes and presents that information to the Controller Module (CM) for use in inventory r

Page 14 - Power Supply

212-Wire Sensor Module (2WSNS)The 2-Wire Sensor Module (2WSNS) is designed to accept 12 sensor inputs per module, and the system as a whole can accept

Page 15 - Relay Module (RLY)

223-Wire Sensor Module (3WSNS)The 3-Wire Sensor Module (3WSNS) is designed to accept 8 sensor inputs per module, and the system as a whole can accept 

Page 16 - AC Input Module (ACI)

234-20mA Analog Input Module (420IB)The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. The TS-550 

Page 17 - Generic Device

24Control Drawing

Page 19 - Standard Terms

26WarrantyFor information concerning Franklin Fueling Systems’s warranties, please refer to the Franklin Fueling Systems Fuel Management Systems Warra

Page 20 - Probe Module (PRB)

27SpecicationsThe TS-550 evo console must be mounted in a location where explosive or ammable vapors are not present, otherwise an explosion hazard

Page 21 - 2-Wire Sensor Module (2WSNS)

©2011 FFS 000-2170 Rev. A

Page 22 - 3-Wire Sensor Module (3WSNS)

3Copyright ©2011 by Franklin Fueling Systems (FFS). No part of this publication may be reproduced in any form without the prior written consent of FFS

Page 23 - 4-20mA Input

4ContentsImportant Safety Messages ...2Notice ...

Page 24 - Control Drawing

5IntroductionThis manual contains installation and site preparation instructions for Franklin Fueling Systems’s TS-550evo console. Overall safety issu

Page 25

6Standard Installation MaterialsRecommended standard materials should be selected and installed per all applicable local, state and federal codes gove

Page 26 - Warranty

7Probe Installation Kit(s)See the TSP-LL2’s installation instructions that came with the probe for the items included with the TSP-K4A standard probe 

Page 27

8TS-550 evo Dimensions and Operating ParametersThe TS-550 evo has conduit knockouts and communication ports located on the bottom of the unit. Use the

Page 28 - ©2011 FFS 000-2170 Rev. A

9Communication PortsThe TS-550 evo console has several communication ports that can be used to communicate with various devices. The communication por