Franklin-fueling-systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setu User Manual

Browse online or download User Manual for Equipment Franklin-fueling-systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setu. Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, & 508) Setup Programming Guide User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 184
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - Leak Detection

Page FC - 1Part Number: 000-1053, Rev. BCopyright © January 2003Setup ProgrammingGuideTank Sentinel ®(TS-1001, 2001, 504, & 508)Automatic Tank

Page 2

PPage P - ii Tank Sentinel Setup Programming GuideBefore You Begin – Read ThisCAUTIONLeaking underground storage tanks ( USTs ) and fuel lines cause s

Page 3 - Table of Contents

Leak Detection Sensors Page 17 - 517Worksheet # 17-2 – Output Groups – Sensor Channels 9 to 16Fill-in the work sheet below and compare assignments wit

Page 4

17Page 17 - 6 Tank Sentinel Setup Programming GuideWorksheet # 17-3 – Output Groups – Sensor Channels 17 to 24Fill-in the work sheet below and compare

Page 5

Leak Detection Sensors Page 17 - 717Worksheet # 17-4 – Output Groups – Sensor Channels 25 to 32Fill-in the work sheet below and compare assignments wi

Page 6

17Page 17 - 8 Tank Sentinel Setup Programming GuideWorksheet # 17-5 – Output Groups – Sensor Channels 33 to 40Fill-in the work sheet below and compare

Page 7

Leak Detection Sensors Page 17 - 917— Your Notes ——❖—

Page 8 - Table of FIGURES and TABLES

Auxiliary Input Setup Page 18 - 118Internally, the TS-1001/504 and the TS-2001/508have two non-intrinsically safe, auxiliary alarminput-channels. The

Page 9 - P PREFACE

18Page 18 - 2 Tank Sentinel Setup Programming GuideAuxiliary Inputs Menu (CONTINUED... FROM PREVIOUS PAG E)AUXILIARY INPUTS Press (M) keys to select I

Page 10 - Before You Begin – Read This

Auxiliary Input Setup Page 18 - 318Worksheet #18-1 – Output Groups – Aux. Inputs 1 and 2Output groups (OG / Out Group) can be assigned to activate an

Page 11 - Key Action

18Page 18 - 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 12 - Alpha-Numeric Input (example)

CPM Setup Page 19 - 11919 Cathodic Protection Monitor (CPM)SETUP PROGRAMMINGCPM MenuRemember:The TS-CPM is programmed from the CPMmenu, which is under

Page 13 - PREFACE Page P - v

PREFACE Page P - iiiPScope of This ManualThis manual shows the setup-programming of Tank Sentinel system. Each Chapter isdedicated to a specific paren

Page 14 - Programming Output Devices:

19Page 19 - 2 Tank Sentinel Setup Programming GuideCPM Menu (Continued ... FROM PREVIOUS PAGE)CATHODIC PROTECTIONDATA Press M1 key.CATHODIC PROTECTION

Page 15 - Optional

CPM Setup Page 19 - 319Worksheet #19-1 – Output Groups – Line Leak TestsFill-in the worksheet below. Compare assignments with other worksheets in the

Page 16 - Warranty Reminder

19Page 19 - 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 17 - 1 System SETUP PROGRAMMING

I/O Module(s) Setup Page 20 - 120The I/O Module menuappears when an optional8 channel, external TS-CIMBriteBox™ is connected tothe console.For TS-2001

Page 18

20Page 20 - 2 Tank Sentinel Setup Programming GuideIIIII / O Module Menu (CONTINUED... FROM PREVIOUS PAG E)IO MODULESGRACE PERI/O MODULE GRACE PERIOD0

Page 19 - System Setup Page 1 - 3

I/O Module(s) Setup Page 20 - 320CAUTION DO NOT use Leak Detection Sensors (i.e. TSP-ULS) with these assembliesor input modules. These are not Intri

Page 20

20Page 20 - 4 Tank Sentinel Setup Programming GuideChannel N Output Groups – Output Module Alarm AssignmentsFor modules assigned as Output Modules (ou

Page 21 - System Setup Page 1 - 5

I/O Module(s) Setup Page 20 - 520N = Output Module Channel Number (typical both pages)9 Fill–in Output Module Channel N = , Alarm Group Assignments B

Page 22

20Page 20 - 6 Tank Sentinel Setup Programming GuideWorksheet #20-1 – Output Groups – For External Inputs onlyFill-in the work sheet below and compare

Page 23

I/O Module(s) Setup Page 20 - 720Worksheet #20-2 – Output Groups – Line Inputs onlyFill-in the work sheet below and compare the assignments with other

Page 24 - 2 Tanks SETUP PROGRAMMING

PPage P - iv Tank Sentinel Setup Programming GuideKey Action (CONTINUED FROM PREVIOUS PAGE... )•ACK SHIFT key is used to change the preconditioned inp

Page 25 - Tanks – TANK DATA N Menu (C

20Page 20 - 8 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 26 - Liquid Level Probe &

Communication Ports Setup Page 21 - 12121 Communication PortsSETUP PROGRAMMINGComm Ports MenuH UMENU× Press this key and follow the7 highlighted seque

Page 27

21Page 21 - 2 Tank Sentinel Setup Programming GuideCOMM PORT 1 Menu (Continued... )BAUD Press M2 key.BAUD RATE9600 BAUDUse UP/DOWN ▲ ▼ keys to show c

Page 28 - Tanks – TANK ALARM N Menu (C

Communication Ports Setup Page 21 - 321COMM PORT 2 MenuUse COMM PORT 2 for remote connection toa POS terminal, or external modem, or to aComputer syst

Page 29

21Page 21 - 4 Tank Sentinel Setup Programming GuideCOMM PORT 2 Menu (Continued... )AUTODIAL (Automatically dials up to 4 numbers whenCOMM 2 AUTODIAL D

Page 30 - ▲▼ keys to scroll thru list

Communication Ports Setup Page 21 - 521COMM PORT 2 Menu (Continued... )DELIVERY (Report Deliveries to:)DELIVERY DIAL STRINGblank up to 4 numbersALARMS

Page 31

21Page 21 - 6 Tank Sentinel Setup Programming GuideDATA MODE Menu (Continued... )AUTODIAL Press M2 key.DATA AUTODIALNUMBER 1 (Automatically dials up

Page 32 - Tank Setup Page 2 - 9

Communication Ports Setup Page 21 - 721DATA MODE Menu (Continued... )DELIVERY (Report Deliveries to:)DELIVERY DIAL STRINGblank up to 4 numbersUse keyp

Page 33

21Page 21 - 8 Tank Sentinel Setup Programming GuideFAX MODE MenuUse the optional internal fax/modem to sendreports to remote Fax machines.Go back / di

Page 34 - 3 Lines SETUP PROGRAMMING

Communication Ports Setup Page 21 - 921FAX MODE Autodial menu ( CONTINUED... )— Press the CANCEL key to return to the FAX AUTODIAL Menu —— Press DOWN

Page 35 - Line Data Menu

PREFACE Page P - vPProgramming Alarms, Limits, or Inputs to Output GroupsThe TS-1001/504 / 2001/508 Tank Sentinels includes a powerful setup feature c

Page 36 - 4 Probes SETUP PROGRAMMING

21Page 21 - 10 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 37 - Probes – PROBE DATA Menu (C

Compliance Via Sensors Setup Page 22 - 122Contents:CVS MenuBefore ProgrammingCVS Tanks MenuCVS Lines MenuSee the Table of Contents to find topics inth

Page 38 - Probes Setup Page 4 - 3

22Page 22 - 2 Tank Sentinel Setup Programming GuideNOTE☞CVS Tanks MenuAfter programming the maximum number of sensors from the SYSTEM menu, accessthe

Page 39 - Probes – SPECIAL Menu

Compliance Via Sensors Setup Page 22 - 322CVS Lines MenuAfter programming the maximum number of sensors from the SYSTEM menu, accessthe CVS Lines menu

Page 40

22Page 22 - 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 41

TS-TPI Setup Programming Page 23 - 12323 TS-TPI SETUP PROGRAMMINGTPI MenuH UMENU× Press this key and follow the7highlighted sequence below ...Cont

Page 42 - 5 Products SETUP PROGRAMMING

23Page 23 - 2 Tank Sentinel Setup Programming GuideTPI PUMP Menu(s)AUTO - CONFIGURATION NOTEThe AUTO CFG function is used to invokethe routines whi

Page 43 - (The SPECIAL PRODUCTS menu

TS-TPI Setup Programming Page 23 - 323The number displayed represents the number ofpump controllers that the TPI device has detected,therefore, it

Page 44

23Page 23 - 4 Tank Sentinel Setup Programming GuidePump N Menu(s)• NAME (user entry)• TYPE “READ ONLY”• GROUP “READ ONLY”• ADDRESS “READ ONLY”• TAN

Page 45

TS-TPI Setup Programming Page 23 - 523— PUMP N Menu continued —TYPE “READ ONLY”Here is the PUMP N menu.Press the M2 key to display the TYPEPUMP N

Page 46 - 6 Manifolds SETUP PROGRAMMING

PPage P - vi Tank Sentinel Setup Programming GuideProgramming Output Devices:After assigning alarms and limits to output group(s), program the appropr

Page 47

23Page 23 - 6 Tank Sentinel Setup Programming GuideThis will allow a pump to be associated with atank. If the pump is not associated with a tank(i

Page 48

TS-TPI Setup Programming Page 23 - 723— PUMP N Menu continued —HEIGHT (user entry)Here is the PUMP N menu, showing TANKand HEIGHT menus...Press th

Page 49 - Example: Man # 1

23Page 23 - 8 Tank Sentinel Setup Programming GuideTPI Group Menu• TYPE “READ ONLY”• MODE (user entry)• RESERVE (user entry)TYPE “READ ONLY”The

Page 50

TS-TPI Setup Programming Page 23 - 923Mode “User Entry” NoteMODE allows the operator to select which Level Management mode to use for a particular

Page 51 - Reconciliation Menu

23Page 23 - 10 Tank Sentinel Setup Programming Guide— TPI Group continued —MODE (user entry)Here is the MODE GROUP 2 user entry fielddisplay. NONE

Page 52

TS-TPI Setup Programming Page 23 - 1123— RESERVE Group N Menu continued —Use the keypad to enter a percent value for each group.Press the ENTER k

Page 53 - PROGRAMMING

23Page 23 - 12 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 54

Upgrade Page 24 - 12424 Upgrade MenuTS-UPGRADEAdditional hardware and/or software features can be added to the Tank Sentinel systemby ordering a TS-UP

Page 55 - DIM Setup Page 8 - 3

24Page 24 - 2 Tank Sentinel Setup Programming GuideCOMMAND(# 3)NUMERICnumber or special character ( # 2 )N...Z( # 1 )A...Minput a letter Press the A

Page 56

Upgrade Page 24 - 324This message will be displayed if anincorrect password was entered.See the WARNING on page 1 of this Chapter...verify that the

Page 57 - (no schedule)

PREFACE Page P - viiPStandard and OptionalOutput DevicesNOTE☞Programming I/O Module OperationThe TS-CIM / TS-IEM channels * can function either as an

Page 58 - Reports Schedule Menu

24Page 24 - 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 59 - Product Usage Summary Report:

Language Page 25 - 12525 Language MenuLanguage MenuH UMENU× Press this key and follow the7highlighted sequence belowContents:Language Selection MenuLa

Page 60 - Delivery History Report:

25Page 25 - 2 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 61 - Alarm History Report:

Data Log Menu Page 26 - 12626 Data Log MenuData Log MenuH UMENU× Press this key and follow the7highlighted sequence belowContents:Data Log MenuData Lo

Page 62 - Reports Schedule Menu (C

26Page 26 - 2 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 63

Display Page 27 - 12727 Display MenuDisplay MenuH UMENU× Press this key and follow the7highlighted sequence belowContents:Display MenuDisplay Navigati

Page 64

27Page 27 - 2 Tank Sentinel Setup Programming GuideDISPLAY Navigation/Descriptions (CONTINUED... FROM PREVIOUS PAGE)Descriptions —Please read the foll

Page 65

Display Page 27 - 327DISPLAY Navigation/Descriptions (CONTINUED... FROM PREVIOUS PAGE)Pump DISPLAY examples:Each controller type will vary in the avai

Page 66

27Page 27 - 4 Tank Sentinel Setup Programming GuideDISPLAY Navigation/Descriptions (CONTINUED... FROM PREVIOUS PAGE)AL-LLD — shows the current status

Page 67

Display Page 27 - 527— Your Notes ——❖—

Page 68

PPage P - viii Tank Sentinel Setup Programming GuideLeaving (Exit) Setup ProgrammingThere are two ways to leave the setup mode. These are:1.) Use (pr

Page 69 - Leak Test Menu (Static Tank)

Diagnostic Menu Page 28 - 12828 Diagnostic MenuDIAG MenuH UMENU× Press this key and follow the7highlighted sequence belowContents:Diag MenuDiag Naviga

Page 70 - Tank Leak Test Menu

28Page 28 - 2 Tank Sentinel Setup Programming GuideTPI Diagnostic Function NotesThe diagnostic function allows the user to command the pump controller

Page 71 - ( no schedule )

Diagnostic Menu Page 28 - 328RESET MenuRESETHere is the SELECT DIAGNOSTIC OPTION menudisplaying RESET, DIPSW and CALIBRT menunames.Press the M1 key un

Page 72 - Tank Leak Test Menu (C

28Page 28 - 4 Tank Sentinel Setup Programming GuideDIPSW MenuDIPSWHere is the SELECT DIAGNOSTIC OPTION menudisplaying RESET, DIPSW and CALIBRT menunam

Page 73

Diagnostic Menu Page 28 - 528CALIBRT MenuCALIBRTHere is the SELECT DIAGNOSTIC OPTION menudisplaying RESET, DIPSW and CALIBRT menunames.Press the M3 ke

Page 74 - Tank Leak Test

28Page 28 - 6 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 75

Problem Solving Page 29 - 12929 Problem Solving (Alarms & Errors)Problem SolvingThe following table lists alarms and errors in alphabetical order.

Page 76

29Page 29 - 2 Tank Sentinel Setup Programming GuideNOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

Page 77 - 12 Line Tests

Problem Solving Page 29 - 329NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }#Printed / Faxed / Dis

Page 78 - 02:05:00 = 2:05 am

29Page 29 - 4 Tank Sentinel Setup Programming GuideNOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

Page 79 - No schedule / not scheduled

System Setup Page 1 - 111 System SETUP PROGRAMMINGSystem MenuH UMENU× Press this key and follow the7highlighted sequence shown belowContents:System Me

Page 80 - See Worksheet 12-1)

Problem Solving Page 29 - 529NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }#Printed / Faxed / Dis

Page 81

29Page 29 - 6 Tank Sentinel Setup Programming GuideNOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }

Page 82 - 13 Clock / Calendar

Problem Solving Page 29 - 729See the Operators Guide for other error messages that are listed by type.Outputs DON’T Turn On When Expected•Printout set

Page 83 - Clock / Calendar Menu

29Page 29 - 8 Tank Sentinel Setup Programming Guide Your Notes ——❖—

Page 84

Appendix A Page A - 1AO/C = Owens Corning / FC Fluid ContainmentD = Diameter (Dia.)L = LengthS = Single WallDW = Double Wall Tank (DWT)A Appendix ASta

Page 85 - 14 Annunciator

APage A - 2 Tank Sentinel Setup Programming GuideTYPECAPACITY DIMENSIONS S / DW# MANUFACTURER MODEL (GALLONS) D x L (INCHES) WALL23 O/C TANKS DWT-2(10

Page 86 - Annunciators Menu (C

Appendix B Page B - 1BB Appendix BStandard ProductsPRODUCT NAME API GRAVITY (6B Compensation)Leaded Regular 63.5Unleaded Regular 63.5Unleaded Plus 62.

Page 87 - Annunciator Setup Page 14 - 3

Page C - 1 Appendix CC—❖—C Appendix CTypical TankLeak Test TimesFor 7 Tank Sizes at Half Capacity (Worst Case is 50% Full)The Leak Threshold value is

Page 88 - 15 Relays SETUP PROGRAMMING

Appendix D Page D - 1DD Appendix DPart Number CodesTank Sentinel Part NumberingThe Tank Sentinel tank gauges and leak detection systems are available

Page 89

DPage D - 2 Tank Sentinel Setup Programming GuideT2PM/8SDCL = TS-2001 with Printer, Modem / 8 tank, SCALD, Data (modem),Canadian, TS-LLD (RS-485 Line

Page 90 - Relays Setup Page 15 - 3

1Page 1 - 2 Tank Sentinel Setup Programming GuideSYSTEM Menu (CONTINUED... FROM PREVIOUS PAG E)SYSTEM ID(enter new 5 line report header, see below)D

Page 91

Customer Feedback Form (front side) Page CFF - 1CFFCFF Customer Feedback FormPlease print these two pages and fill out information about yourself and

Page 92 - 16 TS-ROM Relay Output Module

CFFPage CFF - 2 Customer Feedback Form (back side)Sale and Supply Orders:Please circle (1 = no / poor, 2 = fair, 3 = okay, 4 = good, 5 = yes / excelle

Page 93

FCC Information & Requirements Page FCC - 1FCCFCC Information & RequirementsOverall Information & RequirementsThis equipment complies with

Page 94 - TS-ROM Setup Page 16 - 3

FCCPage FCC - 2 Tank Sentinel Setup Programming GuideINDUSTRY CANADA Information & RequirementsCP-01 Issue 8, Part I, Section 14.1“NOTICE:

Page 95

PO BOX 638SACO ME O40721-800-872-3455 / voice • 1-207-283-0158 / Faxwww.incon.comUSATank Sentinel Setup Programming Guide

Page 96 - 17 Sensors (Leak Detection)

System Setup Page 1 - 31SYSTEM Menu (CONTINUED... FROM PREVIOUS PAG E)NO. SENSORS(enter the number of Leak Detection Sensors)NUMBER OF SENSORS12 (for

Page 97 - Sensors Menu (C

Tank Sentinel Setup Programming GuideNOTICEINCON has strived to produce the finest possible manual for you, and to ensurethat the information containe

Page 98 - +2000.0

1Page 1 - 4 Tank Sentinel Setup Programming GuideSYSTEM Menu (CONTINUED... FROM PREVIOUS PAG E)SENTINEL(after hours theft monitoring / tank leak dete

Page 99 - Sensor Channels 1 to 8

System Setup Page 1 - 51SYSTEM Menu (CONTINUED... FROM PREVIOUS PAG E)REP LINES(Appears only if an L is present in the TS PartREPORT LINE TESTSNumber

Page 100 - Sensor Channels 9 to 16

1Page 1 - 6 Tank Sentinel Setup Programming GuideWorksheet #1-1 – Output Groups – System LimitsFill-in the work sheet below and compare assignments t

Page 101 - Sensor Channels 17 to 24

System Setup Page 1 - 71— Your Notes ——❖—

Page 102 - Sensor Channels 25 to 32

Tank Setup Page 2 - 122 Tanks SETUP PROGRAMMINGTanks MenuH UMENU× Press this key and follow the7highlighted sequence belowContents:Tank Data MenuTank

Page 103 - Sensor Channels 33 to 40

2Page 2 - 2 Tank Sentinel Setup Programming GuideTanks – TANK DATA N Menu (CONTINUED... FROM PREVIOUS PA GE)N refers to / represents a tank numberNAME

Page 104 - — Your Notes —

Tank Setup Page 2 - 32See Figure 2 - 1 at left for typical alarm limitsettings.N refers to / represents a tank number• The alarm copy function copies

Page 105 - 18 Auxiliary Inputs

2Page 2 - 4 Tank Sentinel Setup Programming GuideTanks – TANK DATA N Menu (CONTINUED... FROM PREVIOUS PA GE)TANK ALARM N To select Tank N ...COPY (COP

Page 106 - Auxiliary Inputs Menu (C

Tank Setup Page 2 - 52Tanks – TANK ALARM N Menu (CONTINUED... FROM PREVIOUS PA G E)LL LIM OG N (assign Alarm Limits to Output Group)L L PRODUCT OUTP

Page 107 - OG = Output Group

2Page 2 - 6 Tank Sentinel Setup Programming GuideTanks – SPECIAL TANK N Menu (CONTINUED)SPECIAL TANK N N refers to / represents a tank numberCOPY Pres

Page 108

Table of Contents Page TOC - 1TOCTable of ContentsP Preface...

Page 109

Tank Setup Page 2 - 72Tanks – SPECIAL TANK N Menu (CONTINUED)DELETESELECT POSITION WITH UP/DN POS # Select the POS # to delete (UP/DOWN ▲▼).LEVEL +

Page 110

2Page 2 - 8 Tank Sentinel Setup Programming GuideWorksheet #2-1 – Output Groups – Tanks 1 thru 4Fill-in the work sheet below and compare assignments w

Page 111 - Example:

Tank Setup Page 2 - 92 OG = Output Group- Output Group Assignment WORKSHEET Output Group choices - Tank 5 TS-2001 only:NONE H LIM OG A HH LIM OG B

Page 112

2Page 2 - 10 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 113 - 20 I/O (Input/Output) Module

Lines Setup Page 3 - 133 Lines SETUP PROGRAMMINGLines MenuH UMENU× Press this key and follow the7highlighted sequence belowSELECT MENU OPTION SETUPUP

Page 114 - PREVIOUS

3Page 3 - 2 Tank Sentinel Setup Programming GuideLine Data MenuLINE DATA Select a line.LINE 1LINE 2: Use UP/DOWN ▲ ▼ keys to display Lines 5 – 8.LINE

Page 115 - Y – – Y Y Y – –

Probes Setup Page 4 - 144 Probes SETUP PROGRAMMINGProbes MenuH UMENU× Press this key and follow the7highlighted sequence belowNOTE☞See the Installatio

Page 116 - Channel N Output Groups

4Page 4 - 2 Tank Sentinel Setup Programming GuideProbes – PROBE DATA Menu (CONTINUED... FROM PREVIOUS PA GE)PROBE DATA N PROBE # N shown typical for a

Page 117

Probes Setup Page 4 - 34Probes – PRESSURE PROBE DATA MenuThis grayed out section is a duplicate of the STANDARD menu - use it to assist infollowing th

Page 118

4Page 4 - 4 Tank Sentinel Setup Programming GuideProbes – SPECIAL MenuThe SPECIAL menu appears when at least oneSPEC PROBE N was selected from thePROB

Page 119 - Not with

TOCPage TOC - 2 Tank Sentinel Setup Programming Guide5 Products Setup Programming ... 5 - 1

Page 120

Probes Setup Page 4 - 54Probes – SPECIAL Menu (CONTINUED... FROM PREVIOUS PAGE)Steps:1.) Accurately fill-in TABLE 4.1(ref. Install. Guide / Probe head

Page 121 - 21 Communication Ports

4Page 4 - 6 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 122 - CONTINUED

Products Setup Page 5 - 15Use this menu to specify the productcontained in each tank. See Appendix B forAPI Gravity information – required forSpecial

Page 123 - COMM PORT 2 Menu

5Page 5- 2 Tank Sentinel Setup Programming GuideProduct Data Menu (CONTINUED... FROM PREVIOUS PAG E)COPY FROM PRODUCT DATA X TO N Press (M) key to sel

Page 124

Products Setup Page 5 - 35Special Products Menu (CONTINUED... FROM PREVIOUS PAGE)COPY SPECIAL PRODUCT X TO NPRESS ENTER IF YOU ARE SURE? Press ENTER t

Page 125 - DATA MODE Menu

5Page 5- 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 126

Manifolds Setup Page 6 - 166 Manifolds SETUP PROGRAMMINGManifolds MenuNOTE☞▼ Press the DOWN key ▼See the Table of Contents to find topics inthis manua

Page 127

6Page 6 - 2 Tank Sentinel Setup Programming GuideManifolds Data Menu (CONTINUED... FROM PREVIOUS PAGE)NAME Press M2 key.MANIFOLD NAME NMAN N 9 charac

Page 128 - FAX MODE Menu

Manifolds Setup Page 6 - 36Manifolds ALARMS Menu (CONTINUED... FROM PREVIOUS PAGE)LOW LOW Press M4 key.LOW LOW PRODUCT VOLUME LIMIT N+0.0000 + 0 to 5

Page 129 - 1 and 2

6Page 6 - 4 Tank Sentinel Setup Programming Guide OG = Output Group- Output Group Assignment WORKSHEET Output Group choices -Manifold 1:NONEAB L LI

Page 130

Table of Contents Page TOC - 3TOCMonthly Sales Report: ... 9 - 11Shift Histo

Page 131

Manifolds Setup Page 6 - 56— Your Notes ——❖—

Page 132

Reconciliation Setup Page 7 - 177 Reconciliation SETUP PROGRAMMINGReconciliation MenuH UMENU× Press this key and follow the7highlighted sequence belo

Page 133

7Page 7 - 2 Tank Sentinel Setup Programming GuideReconciliation menu (Continued... FROM PREVIOUS PAGE)RECONCILIATION SCHEDULE Use UP/DOWN ▲ ▼ keys to

Page 134

DIM Setup Page 8 - 18DIM NotesReference the TS-DIM Quick InstallationGuide (pn: 000-1058); especially use section6 to assist in generating the data t

Page 135 - 23 TS-TPI SETUP PROGRAMMING

8Page 8 - 2 Tank Sentinel Setup Programming GuideDIM menu (Continued... FROM PREVIOUS PAGE)FUEL PT ASSOCIATION N1 1 - 16Enter the fuel point number.Us

Page 136 - TPI PUMP Menu(s)

DIM Setup Page 8 - 38DIM menu (Continued... FROM PREVIOUS PAGE)(In most applications using one TS-DIM unit, keep these default settings)FUEL PTS Pres

Page 137 - Number of Pumps Menu

8Page 8 - 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 138 - Pump N Menu(s)

Reports Setup Page 9 - 19Use this menu to program reports to print orFAX automatically on a schedule (faxingrequires an optional Fax/Modem device).Se

Page 139 - M1 M2 M3 M4

9Page 9 - 2 Tank Sentinel Setup Programming GuideReports Schedule MenuTank Inventory Detail Report:TANK INVTANK INVENTORY DETAIL Use UP/DOWN ▲ ▼ to s

Page 140

Reports Setup Page 9 - 39Reports Schedule Menu (CONTINUED... FROM PREVIOUS PAGE)Product Inventory Summary Report:PROD SUMPRODUCT INVENTORY SUMMARY Us

Page 141 - HEIGHT (user entry)

TOCPage TOC - 4 Tank Sentinel Setup Programming GuideTS-ROM Channel 6 Output Group (alarm assignment) ...16 - 3TS-ROM Channel 7 Outp

Page 142 - TPI Group Menu

9Page 9 - 4 Tank Sentinel Setup Programming GuideReports Schedule Menu (CONTINUED... FROM PREVIOUS PAGE)Delivery Detail Report:DEL DETAI DELIVERY DETA

Page 143 - Mode Type and Reserve Note

Reports Setup Page 9 - 59Reports Schedule Menu (CONTINUED... FROM PREVIOUS PAGE)Active Alarm Report:ACT ALRMACTIVE ALARM Use UP/DOWN ▲ ▼ to show cho

Page 144 - Proceed to the RESERVE

9Page 9 - 6 Tank Sentinel Setup Programming GuideReports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)SCALD Leak Test: ReportSCALD* Only with SCALD

Page 145 - Exiting Setup Mode

Reports Setup Page 9 - 79Reports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)Regulatory Report:REGULTORYREGULATORY Use UP/DOWN ▲ ▼ to show choic

Page 146

9Page 9 - 8 Tank Sentinel Setup Programming GuideReports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)Line Test History Report:LINE HIST* Only wit

Page 147 - 24 Upgrade Menu

Reports Setup Page 9 - 99Reports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)Daily Reconciliation Report:DAILY REC* Only with Reconciliation / D

Page 148 - ACK SHIFT

9Page 9 - 10 Tank Sentinel Setup Programming GuideReports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)Daily Reconciliation History Report:DAILY HS

Page 149 - UPGRADE string # 1

Reports Setup Page 9 - 119Reports Schedule Menu (CONTINUED... FROM PREVIOUS PAG E)Monthly Sales Report:SALES REPORT SCHEDULE* Only with Reconciliati

Page 150

9Page 9 - 12 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 151 - 25 Language Menu

Tank Leak Test Setup Page 10 - 110Press the DOWN ▼ key10 Leak Test SETUP PROGRAMMINGLeak Test Menu (Static Tank)H UMENU× Press this key and follow

Page 152

Table of Contents Page TOC - 5TOC24 Language Selection Menu... 24 - 1Language Selectio

Page 153 - 26 Data Log Menu

10Page 10 - 2 Tank Sentinel Setup Programming GuideTank Leak Test MenuN = Tanks 1 – 8 (only the number of tanks programmed inthe System menu will appe

Page 154

Tank Leak Test Setup Page 10 - 310Tank Leak Test Menu (CONTINUED ... FROM PREVIOUS PAGE)Setup automatic leak test schedules for all tanks —SCHEDULE P

Page 155 - 27 Display Menu

10Page 10 - 4 Tank Sentinel Setup Programming GuideTank Leak Test Menu (CONTINUED ... FROM PREVIOUS PAGE)(* This menu appears only when YES was select

Page 156

Tank Leak Test Setup Page 10 - 510 OG = Output Group- Output Group Assignment WORKSHEET Output Group choices - Tank Leak Test:NONETST FL OG Tank

Page 157 - Display Page 27 - 3

SCALD Tank Leak Test Setup Page 11 - 11111 SCALD®Tank Leak TestSETUP PROGRAMMINGSCALD Tank Leak Test MenuH UMENU× Press this key and follow the7highli

Page 158

11Page 11- 2 Tank Sentinel Setup Programming GuideSCALD (tank leak) Test MenuN = Tanks 1 – 8 (only the NO. of TANKSSCALD TESTSprogrammed in the System

Page 159

SCALD Tank Leak Test Setup Page 11 - 311SCALD (tank leak) Test Menu (CONTINUED ... FROM PREVIOUS PAGE)VAPOR RECOVERY (select ENABLED when Vapor Recov

Page 160 - 28 Diagnostic Menu

Clock / Calendar Setup Page 12 - 11212 Line TestsSETUP PROGRAMMINGLN (Line) Tests MenuH UMENU× Press this key and follow the7highlighted sequence belo

Page 161 - TPI Diagnostic Function Notes

12Page 12 - 2 Tank Sentinel Setup Programming GuideLine Leak Test Requirements & Notes:1) Inform the Site Personnel to: (If the store closes at n

Page 162 - RESET Menu

Clock / Calendar Setup Page 12 - 312LN Line (leak) Tests Menu ( Continued from page 1 )* Only the No. of lines that are programmed in System menu are

Page 163 - 1B8C BACKSPACE

TOCPage TOC - 6 Tank Sentinel Setup Programming GuideTable of FIGURES and TABLESPage Layout Convention ...

Page 164 - 1, 2, 3 and so on

12Page 12 - 4 Tank Sentinel Setup Programming GuideLN Line (leak) Tests Menu ( Continued... )* Only the No. of lines that are programmed in System men

Page 165

Clock / Calendar Setup Page 12 - 512Worksheet # 12-1 – Output Groups – Line Leak TestsFill-in the worksheet below. Compare assignments with other wo

Page 166 - Problem Solving

Clock / Calendar Setup Page 13 - 11313 Clock / CalendarSETUP PROGRAMMINGClock / Calendar MenuH UMENU× Press this key and follow the7highlighted sequen

Page 167

13Page 13 - 2 Tank Sentinel Setup Programming GuideClock / Calendar MenuCLOCK/CALENDARDAY SAV Press M1 key.DAYLITE SAVINGS Use UP/DOWN ▲ ▼ keys to sho

Page 168 - Problem Solving Page 29 - 3

Clock / Calendar Setup Page 13 - 313— Your Notes ——❖—

Page 169

Annunciator Setup Page 14 - 114The annunciator menu must be set (DO NOT skipthis menu). The annunciator is an Output Devicethat produces an audible a

Page 170 - Problem Solving Page 29 - 5

14Page 14 - 2 Tank Sentinel Setup Programming GuideAnnunciators Menu (CONTINUED... FROM PREVIOUS PAGE)Modulated Annunciator Output Group (alarm assign

Page 171

Annunciator Setup Page 14 - 314INCON Recommends that you program one of theannunciators to react to system fail warnings and any leakdetection sensors

Page 172 - Problem Solving Page 29 - 7

Relays Setup Page 15 - 11515 Relays SETUP PROGRAMMINGRelay MenuH UMENU× Press this key and follow the7highlighted sequence belowPress the DOWN ▼ key o

Page 173 - Your Notes —

15Page 15- 2 Tank Sentinel Setup Programming GuideRelay Menu (CONTINUED... FROM PREVIOUS PAG E)Relay 1 Output Group (alarm assignment)Select / assign

Page 174 - Standard

PREFACE Page P - iPContents:Graphic Symbol, Page #& Layout ConventionsBefore you Begin– Site Information Required– Other Sources of Info.Page Numb

Page 175

Relays Setup Page 15 - 315Relay Menu (CONTINUED... FROM PREVIOUS PAGE)RELAY 2 Go back to RELAYS menu and push M2 underTIMEOUT RELAY 2 to access this m

Page 176 - Standard Products

15Page 15- 4 Tank Sentinel Setup Programming Guide— Your Notes ——❖—

Page 177 - Leak Test Times

TS-ROM Setup Page 16 - 116This menu appears only after the TS-ROMBriteBox™ is installed, and after console poweris turned on (disregard this Chapter i

Page 178 - Part Number Codes

16Page 16 - 2 Tank Sentinel Setup Programming GuideTS-ROM Menu (CONTINUED... FROM PREVIOUS PAG E)TS-ROM Channel 1 Output Group (alarm assignment)CHANN

Page 179

TS-ROM Setup Page 16 - 316TS-ROM Channel 4 Output Group (alarm assignment)CHANNEL 4TS-ROM CHANNEL 4 Select / assign output group(s) to activateOUT GRP

Page 180 - CFF Customer Feedback Form

16Page 16 - 4 Tank Sentinel Setup Programming GuideTS-ROM Menu (CONTINUED... FROM PREVIOUS PAG E)TS-ROM Channel 8 Output Group (alarm assignment)CHANN

Page 181 - advice !

Leak Detection Sensors Page 17 - 117Internally, the TS-1001/504 has 12 and theTS-2001/508 has 24 IS (intrinsically safe) leakdetection sensor input ch

Page 182

17Page 17 - 2 Tank Sentinel Setup Programming GuideSensors Menu (CONTINUED... FROM PREVIOUS PAG E)SENSORS Press (M) key.AUTO CFG (Automatically identi

Page 183

Leak Detection Sensors Page 17 - 317T SP-ULS T SP-HLSTSP-HIST SP-EISTSP-DISTSP-DDSTSP-DTST SP-DVSTSP-MWSSpecial Vapor Sensor Menu ( Continued... )VAP

Page 184 - SACO ME O4072

17Page 17 - 4 Tank Sentinel Setup Programming GuideWorksheet # 17-1 – Output Groups – Sensor Channels 1 to 8Fill-in the work sheet below and compare a